Why do we have a shunt trip breaker or Isolation contactor in the enclosed Altistart Softstarts (ATS23, ATS46, ATS48, ATS22)?
Issue:
We install either a Shunt trip breaker or Isolation Contactor when building an enclosed or MCC installed softstart.
Product Line:
Altistart 22 (ATS22)
Altistart 48 (ATS48)
Altistart 46 (ATS46) - obsolete
Altistart 23 (ATS23) - obsolete
Environment:
All models, all versions.
Resolution:
This is for line isolation.
All softstarts use SCR's to switch the voltage during operation.
Since the solid-state switches (SCR's) may be incapable of completely blocking incoming power should a failure occur (they will almost always fail shorted), auxiliary isolation on the line-side of the controller is required.
The isolation device must be capable of operation via command from the Fault relay of the controller.
An isolation device consisting of either a circuit breaker incorporating a shunt trip coil or an electromagnetic contactor can be used to open the controller power circuit in the event of a controller fault.
This prevents voltage and current from passing through a damaged SCR and single phasing the motor.
We install either a Shunt trip breaker or Isolation Contactor when building an enclosed or MCC installed softstart.
Product Line:
Altistart 22 (ATS22)
Altistart 48 (ATS48)
Altistart 46 (ATS46) - obsolete
Altistart 23 (ATS23) - obsolete
Environment:
All models, all versions.
Resolution:
This is for line isolation.
All softstarts use SCR's to switch the voltage during operation.
Since the solid-state switches (SCR's) may be incapable of completely blocking incoming power should a failure occur (they will almost always fail shorted), auxiliary isolation on the line-side of the controller is required.
The isolation device must be capable of operation via command from the Fault relay of the controller.
An isolation device consisting of either a circuit breaker incorporating a shunt trip coil or an electromagnetic contactor can be used to open the controller power circuit in the event of a controller fault.
This prevents voltage and current from passing through a damaged SCR and single phasing the motor.
Publicerad för: Schneider Electric Sverige




Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.