Can the Masterpact NW external neutral CT (eNCT) be used on a Masterpact MTZ circuit breaker?
Issue: NW eNCT compatibility with MTZ
Product Line: Circuit Breakers
Environment: Masterpact MTZ
Resolution:
Schneider Electric will not sanction the use of NW ENCT to be used on MTZ because the architecture around the ground is different, and the robustness for EMC and double isolation is different. Use of NW ENCT cannot guarantee unwanted tripping and proper double insulation.
Product Line: Circuit Breakers
Environment: Masterpact MTZ
Resolution:
Schneider Electric will not sanction the use of NW ENCT to be used on MTZ because the architecture around the ground is different, and the robustness for EMC and double isolation is different. Use of NW ENCT cannot guarantee unwanted tripping and proper double insulation.