Ecostruxure Process Expert [2020R2] Error while saving the Supervision Page or Generating Supervision Project

This documents explains how to deal with an error shown below occurred when saving a Supervision Page or Generating Supervision project.

p1

The above shown error might come when using native languages in the system server PC and User had set the option "Unicode UTF-8 for Worldwide language support" in Regional Settings of PC.

In order to resolve this issue, User needs to uncheck option "Unicode UTF-8 for Worldwide language support" in Regional Settings of PC as shown in below screenshot.

p2

This document is applicable for all versions of Ecostruxure Process Expert Software.