Can I use the READ_REMOTE EFB to read data from located or unlocated variables in a Premium PLC?


Issue:
Using the READ_REMOTE EFB to read data from unlocated variables in a Premium or Quantum PLC


Product Line:
EcoStruxure Control Expert


Resolution:
Yes. The READ_REMOTE block will read data from a remote Unity Premium PLC. In the Premium PLC, Data dictionary must be enabled. And in the M340 or M580 PLC where the READ_REMOTE block reside, the second word of the CTRL pin of the READ_REMOTE block must have a value of 1

Setup of the READ_REMOTE blockread_remote_premium.PNG


Premium PLC with data in unlocated variables.
read_remote_premium2.PNG

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings