Control Expert v15 Takes a Long Time to Start Without Internet Connection

Issue:
When launching Control Expert v15.0 SP1, the application takes approximately 5 to 7 minutes to start if there is no internet connection, but only a few seconds when connected to the internet.

Product line:
Control Expert v15.0 SP1

Environnement:
Windows

Resolution:

  1. Press Windows + R, type gpedit.msc, and press Enter to open the Local Group Policy Editor.
  2. Navigate to:
    Computer ConfigurationWindows SettingsSecurity SettingsPublic Key PoliciesCertificate Path Validation Settings
  3. In the Network Retrieval tab:
    • Check "Define these policy settings"
    • Set:
      • Default URL retrieval timeout to 1 (instead of 15)
      • Default path validation cumulative retrieval timeout to 2 (instead of 20)

Certificate Path Validation Settings Properties

4. Apply the changes and restart the system if necessary.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings