Ecostruxure Process Expert[2021]: Unable to connect simulator from remote Engineering Client.

This document explains user what needs to be done when User wants to connect to a Simulator running on System Server from Remote Engineering Client.

When User Runs a simulator on Engineering Server Machine, by default the simulator will run with 127.0.0.1 IP address with a port defined like 502. If user wants to connect the Simulator from Remote Engineering client, then he will not be able to connect.

pc1

In order to have connections from other PCs to Simulator, User need to change the Simulator IP address from 127.0.0.1 to its own host IP address. Example is shown in the below Screenshot.

pc2

Also, ensure that the local windows firewalls are disabled or add firewall rules which should allow the port 502 on both the System server Machine as well as Remote engineering client machine.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings