PowerChute Network Shutdown ESXi host shutdown failed for vSAN standard cluster with Skip Maintenance mode enabled.
Issue:
ESXi host PowerChute Network Shutdown is running on failure to shutdown when configured for vSAN, and enabling Skip Maintenance mode has been selected.
Product:
PowerChute Network Shutdown version 5.x
Environment:
PowerChute deployed onto a vSAN datastore.
VMWare ESXi 7.x or 8.x
Cause:
The PowerChute shutdown delay is set to high.
Solution:
Edit the pcnsconfig.ini file and change the shutdown command duration to 0 (zero) seconds.
Default configuration
[Shutdown]
shutdownCommand =
shutdownCommandDuration = 60
After the change
[Shutdown]
shutdownCommand =
shutdownCommandDuration = 0
ESXi host PowerChute Network Shutdown is running on failure to shutdown when configured for vSAN, and enabling Skip Maintenance mode has been selected.
Product:
PowerChute Network Shutdown version 5.x
Environment:
PowerChute deployed onto a vSAN datastore.
VMWare ESXi 7.x or 8.x
Cause:
The PowerChute shutdown delay is set to high.
Solution:
Edit the pcnsconfig.ini file and change the shutdown command duration to 0 (zero) seconds.
Default configuration
[Shutdown]
shutdownCommand =
shutdownCommandDuration = 60
After the change
[Shutdown]
shutdownCommand =
shutdownCommandDuration = 0
Publicerad för: Schneider Electric Sverige
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.