What are the mandatory DFB pin assignments in EcoStruxure Control Expert V16.0?

Issue

When creating a Derived Function Block (DFB) type in EcoStruxure Control Expert V16.0, some variable types can be entered in the Data Editor but are not supported for DFB pins.

For example, variables declared with the types ANY, ANY_INT, ANY_ARRAY, or ANY_BIT can be created in the Data Editor, but analyzing the DFB will fail.

Product Line

EcoStruxure Control Expert

Environment

EcoStruxure Control Expert V16.0

Resolution

For DFB pins, the following assignments are mandatory for the specified data types:

DFB pinMandatory assignment for
InputDeviceDDT, DDT-Reference, REF_TO
OutputDeviceDDT, DDT-Array, anonymous array (Array of), DDT-Reference, REF_TO
Input/OutputIODDT, DeviceDDT

Assignments not listed above are optional.

Applicable Conditions

The information above applies to DFB types in EcoStruxure Control Expert V16.0.

Do not use ANY, ANY_INT, ANY_ARRAY, or ANY_BIT as DFB pin data types, as these types are not supported and the DFB analysis will fail.