M262 Controller - I/O Red Light always ON.
Issue:
The CPU has On-Board I/O that are not being used and a constant red Light for the I/O status is lit.
Product Line:
TM262 line of controllers.
Resolution:
The error is caused by the outputs not having power connected. To turn OFF the I/O status red light, simply connect a 24Vdc supply to the onboard outputs supply pins.