How to Trigger SBO Relays in the Graphic User Interface GUI
Issue:
Users need to execute Select-Before-Operate (SBO) commands through the SAGE RTU web interface GUI (Config@Web).
Product:
SAGE RTU 14x0, 2x00, 3030, 3030M
Environment:
Config@Web interface w/ HTTPS enabled, proper user roles configured, RTU in Remote mode
Cause:
The SBO command process requires specific steps and permissions within the Config@Web interface to ensure secure and accurate relay operations.
Resolution:
- Log in to the Config@Web interface using a Command-privileged account.
- Navigate to the Command tab and select Control.
- Choose the desired SBO point.
- Set Trip/Close and Execute Time if needed.
- Click Execute to trigger the command.
- Ensure:
- The RTU is in Remote mode.
- HTTPS and user roles are properly configured.
- All actions will be recorded in the Command Log for auditing.
- For detailed instructions, refer to the Config@Web manual (page 172+) attached in the related tab.