Netbotz 750-755 Firmware upgrade requirement for v5.4.x and later

Issue:
Required firmware version before successfully upgrading to 5.4.x and later version and where to download it

Product Line:
NetBotz

Environment:
NBRK0750
NBWL0755

Cause:
When upgrading to newer firmware versions, customers might encounter an error. Upgrading directly from versions prior to v5.3.5 to versions starting from v5.4.x can cause the upgrade to fail.

Resolution:
When upgrading to any version newer than v5.3.5, the appliance needs to be at least on v5.3.5 to upgrade to target version successfully. Attached is the v5.3.5 firmware to enable upgrading an appliance that is currently on 5.3.4 or earlier to latest version.

Schneider Electric Sverige

Bilagor
NBRK075x_Build_5.3.5.434.sedp.7z [373.8 MB]
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings