Downgrading a NetBotz 250A after upgrading to 3.4.2.3 firmware or higher can cause the internal rack access pod to be removed from the UI

Issue:
Downgrading a NetBotz 250A after upgrading to 3.4.2.3 firmware or higher can cause the internal rack access pod to be removed from the UI

Product Line:
NetBotz

Environment:
NBRK0250A
Firmware Version: 3.4.2.3

Cause:
When upgrading the NetBotz 250A to Version: 3.4.2.3, changes to the internal pod's IDs have been made to allow for the connection of extra NetBotz rack access pods. Downgrading to a previous version does not change the ID back so the NetBotz appliance no longer sees the internal pod because of it's new ID.

Resolution:
Disconnect any external pods and re-upgrade to Version: 3.4.2.3 (or higher when available).
After reboot, verify internal rack access pod is visible and proceed in reconnecting any pods.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings