What level of ground fault protection does the ATV320 provide?
Issue:
What type and level of ground fault protection is implemented in the ATV320 drive?
Product Line:
ATV320
Environment:
Ground fault detection operating environment
Resolution:
There are two methods for ground fault detection according to drive size.
For small VSD size, the ground short circuit detection SCF3 is done by a current mirror on the DCBUS current.
The circuit detection compare the current on +DCBUS with the current on -DCBUS.
For bigger VSD size the ground short circuit detection SCF3 is done by homopolar current sensor.
The homopolar current sensor measures the unbalance between the three input phases.
For both methods, the threshold detection is 25% of the nominal inverter current.
This Threshold is fixed value for ATV320 and can't be adjusted.
Publicerad för: Schneider Electric Sverige
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.