What can cause a CFI fault?

Issue:
Display shows CFI

Product Line:
ATV71, ATV71

Environment:
All models and serial numbers

Cause:
Invalid configuration.  The configuration loaded in the drive via the bus or communication network is inconsistent.

Other cause is Max Frequency (tFr) has been set at a value higher than 599 Hz.

Resolution:
For invalid configuration, check the configuration loaded previously or load a compatible configuration.

For Max Frequency (tFr) set to high, set the value lower than 599 Hz.  Due to safey, variable frequency drives cannot run at 600Hz and above.

Schneider Electric Singapore

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Product Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Contact Support
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings