How can we help you today?

What are the changes on the Micrologic trip unit performance when we install a LT Off Rating Plug?

When you use the LR off plug that means Ir = 1 and Tr = very far from standard times delay (near infinity). There is a direct relationship between load shedding and the long time delay protection so for this reason the load shedding will remain off too. You can replace it with the 3 alarms called Ia max, Ib max and Ic max, each alarm have to work in relationship with 3 contacts of the M6C. The power shedding feature is not affected if you install a LT Off Rating Plug

Schneider Electric Singapore

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Product Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Contact Support
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings