ATV61/ATV71: How to take the drive out of PID control mode and put it back into the standard follower mode for AI2 input?
Issue:
How is the drive program changed to disable PID control mode and instead use AI2 analog input for speed reference?

Product Line:

Altivar ATV61 and ATV71

Environment:
All

Cause:
Customer no longer wants the drive in PID control mode.  They want to put it back in standard follower mode.

Resolution:
To take the drive out of PID control mode, go into Menu 1.7 Application menu -> PID regulator, and set PID feedback assignment to NO.
To set reference to follow AI2, go into Menu 1.6 Command menu and set Ref 1 channel to AI2.

Schneider Electric Singapore

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Product Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Contact Support
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings