How to read unallocated variables from M580 or NOC by EIP.

When M580 CPU or NOC as EIP adapter, the Scanner (other PLC or tools) can read its unallocated variable by two ways:
1. Enable the local slaves, and configure the parameter including Instance of Input and Output, and the data size. The scanner can add Class 1 connection by implicit. The scanner can also read by "AssamblyObject"
2. Move the unallocated variable to Modbus Object, and read by "Modbus Object"

Schneider Electric Singapore

Attachment(s)
EIPScan - 2.jpg [22.39 KB]
Explicit_AssemblyObject.jpg [96.98 KB]
M580CPU local slave.jpg [88.53 KB]
DeviceDDT_2.jpg [95.02 KB]
EIPScan - 1.jpg [13.5 KB]
Add Class1 Connection.jpg [27.72 KB]
EIPScan - 3.jpg [75.18 KB]
ModbusObject_2.jpg [125.24 KB]
Add Class1 Connection-2.jpg [35.08 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Product Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Contact Support
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings