MiCOM Px2 - there is no need to use any password for modbus communication
MiCOM Px3 - there is no need to use any password for modbus communication
MiCOM Px4 - there is no need to use any password for modbus communication in the most part of the firmwares
Exceptions are:
In the mentioned above firmwares some read/write commands should be preceded by the level 3 password. The default one is "AAAA" or "AAAA " (41 41 41 41 or 41 41 41 41 20 20 20 20 in hexa).
MiCOM Px3 - there is no need to use any password for modbus communication
MiCOM Px4 - there is no need to use any password for modbus communication in the most part of the firmwares
Exceptions are:
Range | Major Firmware Version |
P14x | 46, A0, B0B |
P24x | D0 |
P34x | B0, E0, B1, E1 |
P44x | C7, E0 |
P44y | D0, F0, D1, F1, D2, F2 |
P54x | D0, D1, D2 |
P64x | 03, B1 |
P74x | B0 |
P746 | B2, C2 |
P841 | C0, D0, C1, D1, C2, D2 |
P849 | B0 |
In the mentioned above firmwares some read/write commands should be preceded by the level 3 password. The default one is "AAAA" or "AAAA " (41 41 41 41 or 41 41 41 41 20 20 20 20 in hexa).
Released for: Schneider Electric Singapore


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.