Issue:
The ATV71 has External Fault assigned to LI5. When active, LI5 trips the drive into External Fault, EPF1. When activating Fault Reset on assigned LI4, the fault is not reset.
Product line:
Altivar 61 Altivar 71
Environment:
All
Cause:
The fault reset needs to come from the assigned Command Channel.
Resolution:
In this case, Command Channel 1 was assigned to a Communications network. So, a Fault Reset needs to come from the Communications Network.
Fault reset by Logic Input is not possible unless the active command channel is Terminals.
Consider temporarily switching the Command Channel to Terminals and then close Logic Input assigned to Reset, or switch to HMI mode and use the local Stop/Reset button (push twice) to reset.
See description / options on the attached file.
The ATV71 has External Fault assigned to LI5. When active, LI5 trips the drive into External Fault, EPF1. When activating Fault Reset on assigned LI4, the fault is not reset.
Product line:
Altivar 61 Altivar 71
Environment:
All
Cause:
The fault reset needs to come from the assigned Command Channel.
Resolution:
In this case, Command Channel 1 was assigned to a Communications network. So, a Fault Reset needs to come from the Communications Network.
Fault reset by Logic Input is not possible unless the active command channel is Terminals.
Consider temporarily switching the Command Channel to Terminals and then close Logic Input assigned to Reset, or switch to HMI mode and use the local Stop/Reset button (push twice) to reset.
See description / options on the attached file.
Released for: Schneider Electric Singapore




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.