How do you configure a relay output on ATV630/930 to indicate safety input status?

Published date: 07 November 2019

Issue:
On the Altivar Process ATV630 and ATV930, we need a relay to indicate if safety input is active or not.

Product Line:
ATV630, ATV930

Environment:
All serial numbers, all model numbers

Cause:
We need to have an indication when the safety circuit on the drive STOA or STOB is open.

Resolution:
You can configure one of the relays of the drive to "Power Removal State":
 
  • Go to Complete Settings
  • Go to Input/Output Relay
  • Go to Rx Configuration
  • Set Rx assignment to "Power Removal State"

Replace x with the number of the relay you want to use.

 