Issue
Is a BMEAHI0821 card only configurable with DHCP in a M580 architecture?
Product Line
BMXEAHI0821
Resolution
The FDR (faulty device replacement) functionality is a feature used by CPU/NOC to assign the same IP and configuration to a new BMEAHI0821 module when replacing a faulty one on the same rack/slot. The module gets its IP only via DHCP (dynamic host configuration protocol) and configuration is transferred from the FDR server of the CPU or NOC.
Is a BMEAHI0821 card only configurable with DHCP in a M580 architecture?
Product Line
BMXEAHI0821
Resolution
The FDR (faulty device replacement) functionality is a feature used by CPU/NOC to assign the same IP and configuration to a new BMEAHI0821 module when replacing a faulty one on the same rack/slot. The module gets its IP only via DHCP (dynamic host configuration protocol) and configuration is transferred from the FDR server of the CPU or NOC.
Released for: Schneider Electric Singapore


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.