Issue:
Converting a Unity Quantum application to an M580 application using the UMAC v2.2 tool
Product Line:
Quantum, Unity Pro, M580, 1MMCSVCZMSXAZZ,
Resolution:
In order to use the the UMAC conversion utility to migrate a Unity quantum application to M580, the user must meet the following criteria.
Prerequisites:
1: The user must have Unity Pro XL =>V12.0 installed on his PC
2: UMAC V2.2 will only accept a Quantum ZEF file created in Unity Pro XL => V12.0
3: Install UMAC and select upgrade to "Standard" mode.
Conversion process
1: Launch the UMAC converter using the "Run as Administrator" option.
2: When prompted, point to the Quantum ZEF file you wish to convert to M580
3: Execute the conversion when prompted by UMAC.
4: Save the converted ZEF file.
5: Generate conversion report from within UMAC.
Converting a Unity Quantum application to an M580 application using the UMAC v2.2 tool
Product Line:
Quantum, Unity Pro, M580, 1MMCSVCZMSXAZZ,
Resolution:
In order to use the the UMAC conversion utility to migrate a Unity quantum application to M580, the user must meet the following criteria.
Prerequisites:
1: The user must have Unity Pro XL =>V12.0 installed on his PC
2: UMAC V2.2 will only accept a Quantum ZEF file created in Unity Pro XL => V12.0
3: Install UMAC and select upgrade to "Standard" mode.
Conversion process
1: Launch the UMAC converter using the "Run as Administrator" option.
2: When prompted, point to the Quantum ZEF file you wish to convert to M580
3: Execute the conversion when prompted by UMAC.
4: Save the converted ZEF file.
5: Generate conversion report from within UMAC.
Released for: Schneider Electric Singapore






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.