Can a logic input be assigned to the external fault in ATV320 drive?

Published date: 09 January 2020

Issue:
Customer needs to configure external fault  ATV320 Drives using logic input.

Product Line:
Altivar  ATV320 drive

Environment:
All 

Cause:
Customer needs to configure external fault ATV320 Drives using logic input.

Resolution:
On the drive display go to DRI- > CONF > FULL > FLT- > EtF- > EtF
then assign (LI1) to (LI6), logic input that is not assigned to any other functions.
Logic can be configured via [External fault config] (LEt) As LO [Active low] (LO) or
HIG [Active high] (HIG) is the default.  It defines the positive or negative logic of
the input assigned to the detected fault. 
Configure EPL [External fault mgt]  for Type of stop in the event of an external fault.
 