"Write to System" is grayed out when trying to write an archive from a "PME 2020 - language Portuguese" into a new "PME 2020 - language Portuguese" - regardless if it is distributed or standalone.
Product Line
Power Monitoring Expert 2020
Environment
Configuration Manager Tool 2020 (CM Tool 2020) - System Migration PME 2020 to PME 2020
Cause
The registry CultureInfoName in a PME system for Portuguese version is set to "pt-BR" however CMTool file that reads the supported versions is using "pt", hence the tool cannot recognize this as a supported path.
Resolution
- Open Configuration Manager Tool 2020 > bin > SupportedVersions.xml in a notepad (make a copy of this file just for safety).
- Search for Languages="pt"
- You will find 4 lines:
- Line 189: <From Version="9.1" InstallationTypes="Distributed" Languages="pt" Editions="" />
- Line 190: <To Version="9.1" InstallationTypes="Distributed" Languages="pt" Editions="" />
- Line 237: <From Version="9.1" InstallationTypes="Standalone,Distributed" Languages="pt" Editions="" />
- Line 238: <To Version="9.1" InstallationTypes="Standalone,Distributed" Languages="pt" Editions="" />
- Replace it for Languages="pt-BR"
- Save it.
Released for: Schneider Electric Singapore


Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales enquiry online and an expert will connect with you.