Issue:
Decelerate the motor with ATS22 Softstarter instead of Freewheel.
Product Line:
ATS22
Environment:
All
Cause:
Need ramp stop
Resolution:
Do not jumper LI1 to LI2. Wire LI1 to CL1, use run contact between CL1 and LI2, and program SEt - dEC = ramp down time.
The factory default setting for the dEC parameter is 'free'.
Decelerate the motor with ATS22 Softstarter instead of Freewheel.
Product Line:
ATS22
Environment:
All
Cause:
Need ramp stop
Resolution:
Do not jumper LI1 to LI2. Wire LI1 to CL1, use run contact between CL1 and LI2, and program SEt - dEC = ramp down time.
The factory default setting for the dEC parameter is 'free'.