After connecting UPS to Windows OS using the USB cable PowerChute Business Edition does not discover the UPS.
Product Line:
PowerChute Business Edition version 10.0.5 and above
Environment:
All supported Windows OS
UPS (SC500RM1U, SMT750RM1U, SMT1000RM1U)
Cause:
For the UPS to be discovered and be able to communicate with PowerChute Business Edition, Silicon Labs USB to Serial driver must be installed prior to installing PowerChute.
Solution:
Download and install the Silicon Labs driver from https://www.silabs.com/documents/public/software/CP210x_Windows_Drivers.zip
.
Steps to Install Silicon Labs driver on GUI based Windows OS
- Download the Silicon Labs driver from the above URL and extract the file.
- Copy the extracted file to the Windows GUI based machine where you wish to install PCBE.
- Navigate to the directory where you have copied the extracted file.
- Determine if you have 32-bit or 64-bit Windows.
- Double click to run the .exe file named CP210xVCPInstaller_xnn.exe(where xnn is x64 for 64-bit and x86 is for 32-bit).
- Follow the instructions
Released for: Schneider Electric Singapore
After connecting UPS to Windows OS using the USB cable PowerChute Business Edition does not discover the UPS.
Product Line:
PowerChute Business Edition version 10.0.5 and above
Environment:
All supported Windows OS
UPS (SC500RM1U, SMT750RM1U, SMT1000RM1U)
Cause:
For the UPS to be discovered and be able to communicate with PowerChute Business Edition, Silicon Labs USB to Serial driver must be installed prior to installing PowerChute.
Solution:
Download and install the Silicon Labs driver from https://www.silabs.com/documents/public/software/CP210x_Windows_Drivers.zip
.
Steps to Install Silicon Labs driver on GUI based Windows OS
- Download the Silicon Labs driver from the above URL and extract the file.
- Copy the extracted file to the Windows GUI based machine where you wish to install PCBE.
- Navigate to the directory where you have copied the extracted file.
- Determine if you have 32-bit or 64-bit Windows.
- Double click to run the .exe file named CP210xVCPInstaller_xnn.exe(where xnn is x64 for 64-bit and x86 is for 32-bit).
- Follow the instructions
Released for: Schneider Electric Singapore




Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales enquiry online and an expert will connect with you.