NetBotz graphs plot only 2 data points

Issue:
NetBotz graphs have only 2 data points

Product Line:
NetBotz

Environment:
NBWL0755
NBRK0750

Cause:
NetBotz sensors that do not change will only show 2 data points in a graph. For instance, a door sensor that has not opened will have a closed State at the beginning of the graph and at the end. No other points will be recorded. The same will be seen for a temperature sensor if the temperature has not changed.

Conversely, if there have been multiple changes, you should see multiple points on the graph.

Resolution:
Upon checking Sensor data history excel, it shows all sensor data captured during this time period.

This function works as designed.

Schneider Electric Singapore

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Product Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Contact Support
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings