Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to address the error code 5 of GOOSE Control Block?
  1. Issue

Customer met with Error code 5 for GOOSE Control Block by using BMENOP0300.
Issue

How to address the issue?
  1. Environment
BMENOP0300
  1. Resolution

Last error 5 means goose time out which indicates the insufficient timeout setting(see below) in the goose configuration.
This is for publisher, the subscriber would decide its "Time Allowed to Live" based on the setting provided by publisher, and subscriber has no para to adjust this .

resolution




Schneider Electric Singapore

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
  • Product Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Contact Support
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings