Why would a drive not stop when the run command is removed?
Issue:
The drive does not stop, when the run command is removed.
Product Line:
Altivar 61, Altivar 71, Altivar 312, Altivar 212, Altivar12, Altivar 32
Environment:
All serial numbers
Cause:
The VFD is not responding to the stop command.
Resolution:
1). Verify how the drive is receiving the stop command.
2). Verify if the drive is programmed to get the stop command from that source.
3). Verify the drive is not in local control.
4). Check if the run signal is jumpered/bypassed
5). Check to see if the motor is backfeeding voltage back into the drive.
The drive does not stop, when the run command is removed.
Product Line:
Altivar 61, Altivar 71, Altivar 312, Altivar 212, Altivar12, Altivar 32
Environment:
All serial numbers
Cause:
The VFD is not responding to the stop command.
Resolution:
1). Verify how the drive is receiving the stop command.
2). Verify if the drive is programmed to get the stop command from that source.
3). Verify the drive is not in local control.
4). Check if the run signal is jumpered/bypassed
5). Check to see if the motor is backfeeding voltage back into the drive.
Publikované pre: Schneider Electric Slovakia
Objavte viac
Rad:
Objavte viac
Rad:
Potrebujete pomoc?
Výber produktov
Rýchlo a jednoducho nájdite tie správne produkty a príslušenstvo pre vaše aplikácie.
Získať ponuku
Kontaktujte nás online a náš odborník sa s vami spojí.
Kde nakúpiť?
Jednoducho nájdite najbližšieho distribútora produktov Schneider Electric vo vašom okolí.
Centrum podpory
Nájdite zdroje podpory pre všetky vaše potreby na jednom mieste.