M580 ERIO architecture and swap behaviour - ERIO Input management

In an M580 ERIO architecture, let’s consider 3 different use cases for Hot Standby hot swap:

1 - Send swap command via DDT control bit -> swap is OK, inputs are properly managed by default / by design
2 - Power off primary rack -> swap is OK, inputs are properly managed by default / by design
3 - Disconnect/remove both ERIO cables on the Primary CPU
Standby will take over, but Inputs bump to 0 could be visible depending on task duration.
If you are concerned by the 3rd use case, to work around this behavior you need to consider the drop health bit: e.g. RACK1_MOD_COM.DROP_COM_HEALTH

Schneider Electric Slovakia

Objavte viac
Rad:
Objavte viac
Rad:

Potrebujete pomoc?

Potrebujete pomoc?

Výber produktov

Výber produktov

Rýchlo a jednoducho nájdite tie správne produkty a príslušenstvo pre vaše aplikácie.

Získať ponuku

Získať ponuku

Kontaktujte nás online a náš odborník sa s vami spojí.

Kde nakúpiť?

Kde nakúpiť?

Jednoducho nájdite najbližšieho distribútora produktov Schneider Electric vo vašom okolí.

Centrum podpory

Centrum podpory

Nájdite zdroje podpory pre všetky vaše potreby na jednom mieste.

  • Produktová dokumentácia
  • Prevzatia softvéru
  • Nástroj pre výber produktov
  • Nahradenie a výmena produktu
  • Centrum nápovedy
  • Nájdite naše pobočky
  • Kde kúpiť
  • Komunita Schneider Electric
  • Kariéra
  • Profil spoločnosti
  • Nahlásiť pochybenie
  • Dostupnosť
  • Redakcia
  • Investori
  • EcoStruxure
  • Vyhľadať pracovné miesta
  • Blog
  • Zásady ochrany osobných údajov
  • Upozornenie o súboroch cookie
  • Zmluvné podmienky
  • Zmeniť nastavenia cookie