What is the function of PLC input ON/OFF on TeSys Giga contactor ?

Normally the contactor operation is controlled by AC or DC control voltage input to A1-A2terminals. But in advanced version contactor, the contactor can be controlled by additional 24V DC PLC inputs to X1-X2-X3 terminals.

When the PLC switch is ON, the contactor function is controlled by PLC input.
When the PLC switch is OFF, the contactor is controlled by control voltage input to A1-A2.


image.png

The electrical schematic and function description are available on the installation guide DOCA0189EN and here is the link:TeSys Giga Series - Contactors and Electronic Overload Relays - Installation Guide User guide | Schneider Electric

Schneider Electric Slovakia

Objavte viac
Rad:
Objavte viac
Rad:

Potrebujete pomoc?

Potrebujete pomoc?

Výber produktov

Výber produktov

Rýchlo a jednoducho nájdite tie správne produkty a príslušenstvo pre vaše aplikácie.

Získať ponuku

Získať ponuku

Kontaktujte nás online a náš odborník sa s vami spojí.

Kde nakúpiť?

Kde nakúpiť?

Jednoducho nájdite najbližšieho distribútora produktov Schneider Electric vo vašom okolí.

Centrum podpory

Centrum podpory

Nájdite zdroje podpory pre všetky vaše potreby na jednom mieste.

  • Produktová dokumentácia
  • Prevzatia softvéru
  • Nástroj pre výber produktov
  • Nahradenie a výmena produktu
  • Centrum nápovedy
  • Nájdite naše pobočky
  • Kde kúpiť
  • Komunita Schneider Electric
  • Kariéra
  • Profil spoločnosti
  • Nahlásiť pochybenie
  • Dostupnosť
  • Redakcia
  • Investori
  • EcoStruxure
  • Vyhľadať pracovné miesta
  • Blog
  • Zásady ochrany osobných údajov
  • Upozornenie o súboroch cookie
  • Zmluvné podmienky
  • Zmeniť nastavenia cookie