EAE25.0: How to enable Secondary NTP server for DPAC Controllers(ATV, M251, M262, M580)

This knowledge base article explains users on How to enable Secondary NTP server for DPAC Controllers (ATV, M251, M262, M580).

By default, User can find only Primary NTP server Configuration in Device Settings as shown in the below screenshot.

ntp1

In order to get the secondary NTP server configuration, User needs to select "Advanced" in Generic settings of Automation Expert Software as shown in below Screenshot.

ntp2

This setting will make other Device configuration settings also visible along with Secondary NTP server Settings and you can enable the Secondary NTP server as shown in below screenshot.

ntp3

Schneider Electric Slovakia

Objavte viac
Rad:
Objavte viac
Rad:

Potrebujete pomoc?

Potrebujete pomoc?

Výber produktov

Výber produktov

Rýchlo a jednoducho nájdite tie správne produkty a príslušenstvo pre vaše aplikácie.

Získať ponuku

Získať ponuku

Kontaktujte nás online a náš odborník sa s vami spojí.

Kde nakúpiť?

Kde nakúpiť?

Jednoducho nájdite najbližšieho distribútora produktov Schneider Electric vo vašom okolí.

Centrum podpory

Centrum podpory

Nájdite zdroje podpory pre všetky vaše potreby na jednom mieste.

  • Produktová dokumentácia
  • Prevzatia softvéru
  • Nástroj pre výber produktov
  • Nahradenie a výmena produktu
  • Centrum nápovedy
  • Nájdite naše pobočky
  • Kde kúpiť
  • Komunita Schneider Electric
  • Kariéra
  • Profil spoločnosti
  • Nahlásiť pochybenie
  • Dostupnosť
  • Redakcia
  • Investori
  • EcoStruxure
  • Vyhľadať pracovné miesta
  • Blog
  • Zásady ochrany osobných údajov
  • Upozornenie o súboroch cookie
  • Zmluvné podmienky
  • Zmeniť nastavenia cookie