我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Directional protection of 2 transformers in parallel: suggested alternative settings to avoid incorrect operation (i.e. spurious tripping) of Sepam units

Goals and Symptoms

Standard setting of angle for directional protection is in this case is 45° but incorrect operation ( (i.e. spurious tripping) can occur with this setting.

Facts and Changes

Key Words and Phrases:
unexpected trips, directional detection, undetected events, non-detection, unwarranted tripping

Causes and Fixes

Attached document explains which alternative settings can be used to avoid spurious tripping.

AEDL3


  • Last Revised: 13 June 2008 by DRM

    Applies To: Operation of Sepam Protection Relays

    Original Author: DM

    Public

    All content © 1992-2008 Schneider Electric


Legacy KB System (APS) Data: RESL191288 V2.0, Originally authored by KBAdPM on 02/27/2008, Last Edited by DaMi on 06/14/2008
Related ranges: Sepam series 80, Sepam series 40, Protection plan

施耐德電機Taiwan

附件
FA179940_Spurious_Operation_of_the_Directional_Phase_Over-Current.pdf [26.97 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings