我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
[OID]Reset=1 does not reset OIDs when tags are in an include project

Goals and Symptoms

Summary:
It was found that setting [OID]Reset=1 in the Citect ini file, did not reset the OIDs when the variable tags are located in an include project.
I've used Open Office to modify my variable.dbf.

This behaviour also exists when using the ProjectDBFAddIn macro with the 'Save Only" option.
Using the "Save and Reindex" option however allowed the OIDs to be reset

I'm able to reset without any problems if the variable tags are located in the main project after I've modified the variable.dbf using
- Open Office
- ProjectDBFAddIn macro with the 'Save Only" option

Facts and Changes

Keywords:
OIDs, OIDs do not reset, Open Office, ProjectDBFAddIn, [OID]reset=1

Causes and Fixes

Solution:
- Have the variable tags in the main project if you are using
- Open Office
- Use the ProjectDBFAddIn macro with the "Save and Reindex" option


Ctiect is aware of this problem and we are currently investigating this issue.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings