我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How often does a GPS time sync an ION meter?

The meter uses every fifth GPS time sync packet received over comms for time syncing. After the GPS locks, the meter will perform a time set if:
1. the time has drifted more than one millisecond
2. the time since the last time sync is greater than the product of twice the average time between time syncs for the previous five time syncs.

If the drift was less than 1 second, the time sync is not recorded in the meter event log (minor adjustment). If the time drift is greater than 1 second, the time sync will be recorded in the meter event log (major adjustment).

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings