我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to Log the Modem Interaction for an Internal Modem on an ION Meter

Issue:
How to log Modem interactions

Product Line:
ION8600
ION7300
ION8500
ION8400
ION8300
ION7550/ION7650
ION8800
ION7500/ION7600

Environment:
Hyper Terminal

Cause:
To troubleshoot internal ION Modems, complete the following procedure then analyze the different strings.

Resolution:
Make two connections to the meter: COM1 via RS232/485 and the modem via RJ11

  1. Switch COM1 protocol to Modemgate
  2. Open a HyperTerminal session to COM1
  3. To see the typed text and responses, select File > Properties > ASCII Setup > and check the 'Echo typed characters locally' box > click OK

  4. Log the entire connection (Transfer> Capture Text)
  5. Power cycle the meter. In HyperTerminal there will be some init strings with some OK responses, wait until it is done
  6. Type ati0 (to get the modem type)
  7. Type at&v (to get the current settings)
  8. Dial into the meter via modem. In HyperTerminal you should see RING, then hear a bunch of squawking (the modem establishing a connection) if there is a speaker. At this stage do not press any keys; it will list the negotiation parameters.
  9. Disconnect the site. You should see a disconnect message in HyperTerminal
  10. Ensure the LED lights on the side of the meter go out. If they don't type ath0

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings