Ethernet ports and socket summary on ION meters

Article available in these languages:

Issue
A user would like to know the total allowable simultaneous connections on ION meters

Product Line
ION Meters ( 9000, 8800, 8650/8600, 7650/7550, 7350/7330/7300, 7700, ACM3720) and PM8000

Environment
TCP/IP network sockets
Cause
User didn't that they can have one or multiple simultaneous connections on powerlogic and ION meters

Resolution

The table below summarizes the Ethernet Ports (sockets) available on ION meters

Meter(s)Total Allowable Simultaneous ConnectionsProtocolTCP Port / socketMaximum Connections per Protocol
ION90008 connections total allocated to all protocolsION7700 8
EtherGate (Com1)7801 1
EtherGate (Com4)7802 1
DNP20000 3
IEC 61850102 5
Modbus TCP502 8
Modbus RTU7701 8
Telnet23 1
FTP21 2
Webserver (HTTP)80 10
Secure webserver (HTTPS)443 10
PM80008 connections total allocated to all protocolsION7700 8
EtherGate COM17801 1
DNP 3.020000 3
IEC 61850102 5
Modbus TCP502 32
Modbus RTU7701 4
Telnet23 1
FTP21 1
Web server (HTTP)80 1
ION 86508 connections total allocated to all protocolsION7700 8
EtherGate COM17801 1
EtherGate COM47802 1
DNP 3.020000 3
IEC 61850102 5
Modbus TCP502 8
Modbus RTU7701 8
Telnet23 1
FTP21 1
Web server (HTTP)80 1
ION 8600(V330)
, 8800(V334)
4 connections total allocated to all the protocolsION7700 4
Modbus RTU7701 4
Modbus TCP502 4
EtherGate COM17801 1
EtherGate COM27802 1
Telnet23 1
DNP20000 3
Modbus Master502 10
ION 7500, 7550*
7600, 7650*
8300, 8400 8500
* Firmware revisions prior to V350
4 connections total allocated to all the protocolsION7700 4
Modbus RTU7701 4
Modbus TCP502 4
EtherGate COM17801 1
EtherGate COM27802 1
Telnet23 1
ION 7550*, 7650*
With V350 Firmware
4 pooled socket connections in total allocated to all the protocolsION7700 4
Modbus RTU7701 4
EtherGate COM17801 1
EtherGate COM27802 1
Telnet23 1
DNP20000 3
Modbus TCP*502 32
ION 7700 / Xpress Card1 max connection from either: ION or Modbus RTU.
1 max telnet session, independent of other connections.
ION7700 1
Modbus RTU7700 1
EtherGate COM2 and COM3 simultaneously7800 1
EtherGate COM2 only7802 1
EtherGate COM3 only7803 1
Telnet23 1
ION 7300, 7330, 7350-1 max dedicated ethergate connection
-1 max connection from either: Telnet, ION Modbus RTU or Modbus TCP
- The EtherGate and ION/etc connections are independent of each other (i.e. not pooled together)
ION7700 1
Modbus RTU7701 1
ModBus TCP502 1
EtherGate - COM27802 1
Telnet23 1
ACM 37203720 Protocol3721 1 to 3
Modbus RTU3722 1 to 3
Telnet23 1