Issue

How to map MWh values to DNP slave export modules using ION Setup

Product Line

ION Setup

Cause

On a meter without a Megawatt option, it is possible to link a Mwh value/register to DNP slave export module (or any other module needed) utilizing an arithmetic module and a periodic timer module.

Resolution

Log in to ION Setup.

Save the template you currently have with the kWh settings somewhere on your system

setup assistant

Exit the setup assistant (indicate that you don't want to connect to another meter)

save

While holding the CTRL key, click on the device on your device (on the left hand side of the screen) > all the modules in the advanced mode should appear

Ethernet Device Ethernet Device

Select the Arithmetic Modules > Right click on the right hand side, and Insert a new module

Arithmetic Modules Insert Module

Double click on the module (should have an X going across it) and get into the setup screen (click OK when the warning shows up)

Arithmetic 20 Modification Warning

Insert a new source to Source 1 by double clicking on the "Source 1:" (kWh > this can be found in Integrator module)

Arithmetic 20 (OFF-LINE) ION Input Selection


Insert the "Period Timer" (or you could create your own timer) to the "CalcNow" section (the Period timer is a 1 second timer)

CalcNow kWh del

Click on the "Setup Registers tab" > Insert the "S1/1000" formula into the ART# Formula 1

ART20 Formula 1

Click on the "Output Registers tab" > Edit the "ART#Result 1" to Mwh Output Registers

Send

ART20

Right click on the Arithmetic Module # and Rename it to "Mwh Scaling"

Rename Mwh Scaling

Send

Select the DNP Slave Export Modules > Right Click and Insert a new module

DNP Slave Export Modules

Double Click on the new module > Edit the Source 1 > Select Arithmetic Modules > Mwh Scaling > Mwh

ION Input Selection Source 1

You may then modify your Setup Registers as deemed fit.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings