Troubleshooting of modbus communication to a serial device connected through an EGX100 or EGX300

Issue
Troubleshooting of Modbus communication to a serial device connected through an EGX100 or EGX300

Product Line
EGX100, EGX300

Environment
EGX web server, dip switches, and wiring

Cause
Physical wiring, dip switch configuration settings, and the EGX web server configuration must be correct in order for correct communications.


Resolution
Wiring

The EGX supports both 2-wire and 4-wire configurations provided dip switch settings are correct and serial port settings match. The EGX installation guide includes details about wiring 2-wire and 4-wire systems. If a 4-wire device needs to be connected to a 2 wire configured EGX, bridge RX+ with TX+ on the device, and connect this to the Rx+ connection on the EGX. Similarly, bridge RX- with TX- on the device, and connect this to the Rx- connection on the EGX.

Dip Switches
The EGX dip switch configuration for the RS-485 Biasing and Termination should be set to match the system as described below.
Dip Switch Configuration
Figure 1: Dip Switch Configuration For 2 or 4-wire Devices

EGX web server configuration
To access the configuration section for the EGX serial port access the EGX web server by typing the IP address into a web browser. Navigate to Setup->Serial Port
Serial Port

Figure 2: Serial port configuration on EGX web server

  • Ensure the Physical Interface is appropriately set for 2 or 4-wire.
  • Ensure the Baud Rate matches the rate that the serial device is configured for.
  • Ensure the Parity matches the parity that the serial device is configured for.
Access the Device List located in Setup->Device List on the EGX Web server
  • If the Unit ID of the meter trying to connect is not entered into the Device List of the web browser, then add it.


NOTE: Unit ID is not recommended to be set to 100. The reason being that Unit ID 100 is reserved for Modbus TCP connection.

Verifying Successful Communication
The 3 screen shots below displays what the correct configuration will result in.

Read Registers from EGX web server :
Go to Diagnostics->Read Device Registers
Reading device registers on the EGX Web Server
Figure 3: Reading device registers on the EGX web server

Read registers with mbmasterv21m3:
Reading device registers with mbmaster
Figure 4: Reading device registers with mbmaster

Read registers with Modbus Tester:
Reading device registers with Modbus Tester
Figure 5: Reading device registers with Modbus Tester

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings