What are the default values logged in the EGX400 and EGX200?

Issue
What values are logged by default from EGX200 or EGX400?

Product Line
EGX400
EGX200

Environment
Onboard Logging

Resolution
NOTE: The EGX200 does not have device logging.

The EGX400 ships from the factory with device profiles for standard Schneider Electric monitoring and protective devices.

Click the following link: EGX200/400 User's Guide | Schneider Electric , and refer to page 3 under "EGX400 Device List" for a list of supported devices and logged data.

Real energy, reactive energy, and apparent energy are logged by default for Schneider Electric Monitoring devices. For example, the EGX400 logs Real Energy and Real Power Demand for the Enercept and Energy Meter.

The EGX400 can log data at predefined intervals from up to 32 serially connected devices. For details, see "Device Logging" on page 5 and “Interval Data Logging (EGX400)” on page 13 of User guide.

NOTE: The Series 200 Power Meter (PM210) is not a loggable device type in the EGX400 with firmware v5.6. A device type template (.plt) file will be created at a later date. A temporarily work around is to select the PM700 device type for the PM200 meter and then enable logging. The PM700 and the PM200 share some of the same registers. Some PM700 quantities may not be applicable for the PM200.

施耐德電機Taiwan

附件
EGX200_EGX400 User Guide.pdf [1.13 MB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings