In an ION meter's data sheet, what does "%rdg + %FS" for meter accuracy mean?

Issue
User is looking for details regarding meter accuracy from data sheets, %rdg + %FS

Product
ION Meters

Environment
Technical data sheets

Resolution
The meaning of %rdg + %FS is % Reading + % Full Scale.

  • Here is a quick example of the application of this method of calculating the potential error range for a current reading:

    =======================================================

EXAMPLE SITUATION

Let's say we have a situation where:

* The meter under consideration is an ION 7350 which specifies the accuracy of the current reading in the datasheet as 0.25% of reading + 0.05% of full scale as can be seen excerpt from an old meter datasheet immediately below.

Spec information from datasheet

  • * The meter is wired to the electrical system using CTs of the ratio 200:5

* The meter is reading a primary current value of 103.85 A

QUESTION

How would one calculate the expected error bound of this meter reading?

ANSWER

In order to make the calculation, we need a value for the full scale current. The specification of the current inputs to the meter shows the following data at another place in the datasheet:
current inputs
Thus, the full scale value of the meter reading would be 10A on the input * the CT ratio which is 200 / 5 = 400 A.

So now the calculation of the error is as follows:

potential reading error = 0.25% of reading + 0.05% of full scale = 0.25% of 103.85 A + 0.05% of 400A = 0025 x 103.85 + 0.0005 x 400 = 0.259625 + 0.2 = 0.46

So when the meter reads 103.85 Amperes, the potential error of that reading is +/- 0.46 A.
=========================================================

NOTE: For the sake of simplicity, the above calculation excludes the potential error introduced into the measurement system by the instrument transformer. Naturally, the instrument transformer has an accuracy rating of its own. The error of that instrument would be added to the of the meter. Thus if the instrument transformers error rating was +/- 5 % of reading, this number would be added to value already calculated. In this case, a reading of 103.85 A would have an error of +/- 5.19 A. Thus combined error for current readings of the entire measurement system (i.e. the combination or the CTs and the ION meter) would be 0.46 + 5.19 = +/-5.65 A.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings