Is it possible to change application type of my Sepam?

Issue
A new protection application type is need for the existing Sepam.

Product Line
Sepam series 20
Sepam series 40
Sepam series 80

Environment
Application Type

Resolution
The answer is a little bit different according to the Sepam series:

  • ​Sepam series 20 and 40: Modification of Sepam application type requires replacement of your complete Sepam. You need to order a new PowerLogic Protection Relay with the correct application type needed.
  • Sepam series 60 and 80: As application type is in the cartridge, modification of Sepam application type requires only replacement of the cartridge. You need to order a new cartridge with the application type needed. Note: be careful, since you may need to purchase additional CCA63x CT adapters, depending on which Application Types are involved.

Note that in all cases, a firmware patch cannot modify application type of a Sepam.

Update Note (April 2026).

The Sepam 20/40 range is obsolete and has been replaced by the PowerLogic P3 / P5 line, depending on the application. Likewise, the Sepam 60/80 range is in the final stage of its commercial life, and for new projects it can be replaced by the PowerLogic P7.