我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Sepam ECI850 Server - can I use the same CID files as for the PowerLogic G3200 Gateway?

Schneider Electric offers a wide variety of solutions to enable users to utilize the IEC61850 communication protocol with their products.

For existing installations with devices that have only 2-wire RS-485 Modbus capability, two products presently offered (as of 2012) are the Sepam ECI850 Server and the PowerLogic G3200 Gateway.  Since these 2 products are very similar in appearance, some users may ask if they are completely interchangeable. This FAQ provides some details on this question as it pertains to IEC61850 configuration.

1) Sepam ECI850 Server

This server was primarily designed to work with the Sepam Series 20, 40, and 80 relays.  It is an Ethernet to RS-485 (Serial) converter with default libraries that enable communication with Sepam relays.  To build CID files for communication with Sepam relays, the following Schneider Electric software utilities can be used: SFT2841 and CET850 V2.1 (or higher).  If SFT2841 is used, certain IEC61850 parameters (such as Report Control Blocks and Datasets) cannot be configured.  Presently, the SFT2841 software includes primarily libraries for the Sepam relays, and it does not have libraries for other devices such as PowerLogic-ION meters.

2) PowerLogic G3200 Gateway

This gateway was developed to communicate with a wider range of Schneider Electric products.  It is also an Ethernet to RS-485 (Serial) converter, but the firmware is significantly different compared to the ECI850 Server.  In addition to having drivers for standard products such as the Sepam relays and PowerLogic-ION meters, this gateway can support custom device types and legacy products such as the Sepam 2000.

To configure CID files for the G3200, the CET850 V2.1 (or higher) software should be used.  Presently, the Sepam SFT2841 software does not include default libraries that enable the user to build CID files for the G3200 gateway.

To summarize, regarding IEC61850 configuration, CID files for a given device should be built only using the software designed specifically for that device, and they cannot be ported from one type of device to another (unless specifically stated in the product documentation).  So, ECI850 and G3200 CID files are not interchangeable, and the user should use the correct software and ICD templates for each device when starting a new project.



AEDL3

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings