Error 2738 retruned when installing the 'PROFIBUSRemoteMasterV1.3' software

Issue
'Error 2738.Could not access VBScript run time for custom action' is returned while trying to install the 'PROFIBUSRemoteMasterV1.3' software

Product Line
TCSEGPA23F14F

Environment
Windows 10

Resolution
'Error 2738.Could not access VBScript run time for custom action' gets returned during the installation of the  'PROFIBUSRemoteMasterV1.3' software,





This error message indicates that the VBScript engine is either not registered or has an incorrect value in the registry for the PC operating system.  This is a Windows operating system related issue and has nothing to do with the  'PROFIBUSRemoteMasterV1.3' software.   If you do a search on the web, you will get a list of articles regarding this error.

To resolve the issue you can try one of the the following
  • Perform a clean boot of the PC and then try installing the DFB again.
  • Register the VBScript engine (vbscript.dll ).



To register the vbscript.dll:
  • Log  into the PC as a Windows system administrator.
  • Click on Start Menu -> All Programs -> Accessories
  • Right click on 'Command Prompt' and select 'Run as administrator'.



  • Change the pathname to the appropriate pathname for the location (see note below) of the 'vbscript.dll' file.
  • Type 'regsvr32 vbscript.dll' into the Command Prompt and hit Enter





Note:          If you are using 32-bit version of Windows:

Type cd %windir%\system32 into the Command Prompt and hit Enter

If you are using 64-bit version of Windows:

Type cd %windir%\syswow64 into the Command Prompt and hit Enter




If the above procedures fails to resolve the issue, try
  • Log  into the PC as a Windows system administrator.
  • Backup the registry or create a restore point.
  • Click on Start Menu -> All Programs -> Accessories
  • Right click on 'Command Prompt' and select 'Run as administrator'.


  • Type in 'Regedt32' and hit Enter to open the Registry Editor.



  • Click on 'HKEY_LOCAL_MACHINE\SOFTWARE\Classes\Wow6432Node\CLSID'



  • Locate the registry key named '{B54F3741-5B07-11CF-A4B0-00AA004A55E8}'
  • Right click on the key named '(B54F3741-5B07-11CF-A4B0-00AA004A55E8)'
  • Click on 'Delete.   (This  removes the incorrect entry for VBScript support on 64-bit Windows 7).
  • Close the 'Registry Editor'.


Note:        Be careful when editing the registry for the Windows operating system.  If the instructions are not followed exactly,
you could corrupt the registry and make the PC inoperable.  If you corrupt the operating system, Schneider
Electric cannot be held liable.


  • Click on Start Menu -> All Programs -> Accessories
  • Right click on 'Command Prompt' and select 'Run as administrator'.
  • Change the pathname to the appropriate pathname for the location of the 'vbscript.dll' file.
  • Type 'regsvr32 vbscript.dll' into the Command Prompt and hit Enter





If this does not resolve the issue, you may need to try it on another PC.

For further reading, reference the following articles on the web.:
  • https://support.cch.com/kb/solution.aspx/sw17516
  • http://answers.microsoft.com/en-us/windows/forum/windows_7-windows_programs/error-2738-could-not-access-vbscript-run-time-for/1a4499ae-8bc1-4534-9c6f-4d399ac70d9a
  • https://knowledge.autodesk.com/support/autocad/troubleshooting/caas/sfdcarticles/sfdcarticles/Installation-fails-with-message-Error-2738-Could-not-access-VBScript-run-time-for-custom-action-s.html
  • http://www.instant-registry-fixes.org/how-to-resolve-error-2738/
  • https://support.microsoft.com/en-us/kb/929135.
  • https://answers.microsoft.com/en-us/windows/forum/windows_7-windows_programs/error-2738-could-not-access-vbscript-runtime-for/64ae2fd3-2701-4731-88fa-773ba88a74af

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings