我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Why don't my Structured Text Timers reset?

Issue
Why don't my  Structured Text Timers  reset?

Product Line
EcoStruxure Control Expert

Environment
Control Expert v14.1


Resolution
If you are used to high level languages for a computer, some things in PLCs are not immediately obvious. For some developers timers are one of them. In a timer such as the TON procedure the first parameter is a Boolean that controls the timer. If it is True,  the timer runs. However, the timer is solved and the clock is reset if the parameter is False.  This putting the timer within a conditional will prevent the timer from resetting.
The following code snippet will run to 10 seconds and then continue:
im1

The following will run for 10 seconds and stop:
im2

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings