How to fix problem when TSXCUSB485 or TSXCUSB232 cable is not recognized by windows 10?

Article available in these languages: Czech, 希臘文, 匈牙利文, 荷蘭文

Issue
Windows 10 doesn't recognize the connection cable TSXCUSB485 or TSXCUSB232.

Product Line
EcoStruxure Control Expert, TSXCUSB485, TSXCUSB232

Environment
TSXCUSB485, Windows 10

Resolution
Be sure you have administrator rights. The most probable reason is that windows provides the driver from windows update site instead of using the driver from SchneiderModbusDriverSuite (part of Unity Pro/ControExpert installation).
  1. In Device manager, uninstall TSX cable driver (in Serial USB folder) when TSXCUSB485/TSXCUSB232 cable is plugged in.
  2. Open Control Panel>> System>> Advanced system settings>> Hardware>> Device installation setting and select "no" for the option "Do you want to automatically download manufacturers apps and custom icons available for your device?"
  3. Uninstall Driver Manager x64. (search DriverManager x64 in registry HKEY_LOCAL_MACHINE\Software\Microsoft\Windows\CurrentVersion\Uninstall, then copy the uninstall string (msexec...) and run it
  4. Unplug the TSX cable, restart PC
  5. Run "Turn windows features on or off" and check if microsoft  .NET framework is enabled including 2 sub options (Foundation HTTP activation, Framework activation)
  6. Install the driver (schneiderModbusDriverSuite 14_12 or newer) or re-install Unity Pro completely.
  7. Plug in TSX cable and check in device manager if the cable appears in com port folder. If so, problem is solved.
P.S.: You can see the drivers inside of the instalation folder:
image

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings