How to perform an Auto-Diagnostics Test on an ATV61 or ATV71 Drive?

Resolution:
The ATV61/ATV71 drives include a built-in diagnostics feature that allows you to test internal components, such as IGBTs and thyristors. This is useful when troubleshooting issues like short circuit faults or verifying the health of the drive.

Run the auto-diagnostics test if you experience:

  • Short circuit faults
  • Suspected internal component failure
  • Unexplained drive behavior

1.- Access the Diagnostics Menu

  • Navigate to: Menu 1.10 – DIAGNOSTICS

Navigation to Menu 1.10- Diagnostics
2.- Select Test Procedures

  • Choose “Test Procedures” from the menu
  • Select the specific test you want to run

3.- Start the Test

  • A warning message will appear
  • Press and hold the ENT (Enter) key for 2 seconds to begin


Navigation to select procedure and start the test.
4.- Understanding Test Results

For each IGBT tested, results are displayed on two lines:

  • Line 1: Indicates if a short circuit is detected
  • Line 2: Indicates if the component is open (no continuity)

Technical note:
The [TEST THYRISTORS] option is only available for:

  • ATV61 drives ≥ 18.5 kW (M3 and N4 ranges)
  • All ATV61...Y models

Extended test results (Thyristors 4–12 and IGBTs 1B–6B) are only available for:

  • ATV61EC90N4 to M14N4
  • ATV61EM15Y to M24Y

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings