PME - Trends not loading real-time data with error "Cannot retrieve any data"

Issue

In the PME Web Applications, real-time data doesn't load in Trends. Clicking on the flashing exclamation point icon shows "Cannot retrieve any data. Ensure that all required services are running on the server."

Cannot retrieve any data

Product Line

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment

Web Applications

Trends

Internet Information Services (IIS)

Cause 1

A required ION service isn't running.

Resolution 1

1. Open the Windows Start Menu, then search for and open Services.

2. Check that all services starting with the word "ION" that also have a Startup Type of "Automatic" or "Automatic (Delayed)" are Running. If any are stopped, start them.

Cause 2

Various configuration errors with the Web.config files used for the PME web server can cause this problem. The below steps show how to resolve one possible configuration error as an example.

Resolution 2

*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

1. In the Web Applications, navigate to the Settings tab > System > System Log.

  • Note: If on PME 9.0, refer to the steps at this article for how to use the Diagnostics Tool: https://www.se.com/us/en/faqs/FA275753/
  • To output this log using the Diagnostics Tool, select only the "AppMods Diagnostics" output and uncheck "Compress package". Then, you can view the log by opening the AppMods Diagnostics.html file in the Outputs folder of the generated diagnostic.

2. Use the Minimum Priority dropdown to filter for "Error", then look for an error that mentions a URL for one of PME's web components. Note the web component shown after the server name in the URL, for example http://localhost/WebServices/WebRealTime.svc indicates the problem is with the WebServices page:

System log error

3. Open the Windows Start Menu, then search for and open Internet Information Services (IIS).

4. Expand the server name > Sites > Default Web Site, then select the page mentioned in the error message. Double-click on Error Pages:

IIS web page configuration

5. Click Edit Feature Settings..., select Detailed Errors then click OK:

Enable Detailed Errors

6. Select the page in the left pane again, then click Browse *:443 (https)

Select the WebServices page and click Browse

7. The web page opens displaying a configuration error. Note the Error Message, Source Error, and Source File to determine which Web.config file and what the issue is. In the following example, it shows:

  • Error Message: "A child element named 'service' with same key already exists at the same configuration scope. Collection elements must be unique within the same configuration scope (e.g. the same application.config file). Duplicate key value:  'PowerQuality.Analytics'."
  • Source Error: (location of the issue in the file)
  • Source File: C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\WebServices\web.config

Error for WebServices page

8. Open File Explorer, then navigate to the location of the Web.config file. In this example it's C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\WebServices\web.config

9. Open the Web.config file in Notepad:

10. Refer to the Source Error on the web page and navigate to the same location in the Web.config file, then refer back to the Error Message to identify the configuration issue. In this example, the error mentioned Duplicate key value: 'PowerQuality.Analytics', so to resolve this error, delete the duplicate section for 'PowerQuality.Analytics':

Duplicate value in Web.config file

11. Go to File > Save As, then save onto the Desktop since the folder won't allow overwriting the file directly:

Save modified web.config to desktop

12. Move the saved file into the location of the original Web.config file to overwrite it:

Overwrite with file from desktop

13. Open the Windows Start Menu, then search for Command Prompt. Right-click on Command Prompt > Run as Administrator

14. Run the following command: iisreset

15. Open Services and restart the ION Application Modules Core Services Host service. Click Yes when asked to restart the ION Application Modules services.

16. Close and reopen the web browser.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings