我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What is the difference between Cascading Rack APDUs 10K and using the Redundant Network Access (RNA)?

Question:
What is the difference between Cascading Rack APDUs 10K and using the Redundant Network Access (RNA)?

Product:
APC by Schneider Electric APDU10K NetShelter® Rack PDU Advanced - all serial numbers


Solution:

There will be some instances that a customer would like to cascade an APC by Schneider Electric NetShelter® Rack PDU Advanced to either achieve centralized control and monitoring OR redundancy in terms of the IP / remote access.

There are 2 options a customer would want to use.

  1. Cascading - In cascade mode, up to 32 Rack PDUs can be connected using one (1) IP address. Information and data from all Guest Rack PDUs is gathered from the Host Rack PDU. Cascade functionality reduces the network services cost for Rack PDUs. For example, a standard network switch is used in a data center can contain 24 ports. Without using the cascade function each port supplies network services to one (1) Rack PDU. Using the cascade features, a typical network switch with 24 ports can supply network services for up to 768 Rack PDUs.
    The following image shows an example diagram for cascading NetShelter APDU Advanced
  2. Redundant Network Access (RNA) - The Redundant Network Access allows secure access of Rack PDU data and statistics on two (2) separate private networks. RNA is used with a redundant power delivery design including two (2) Rack PDUs for each Track. The Rack PDUs must be the same SKUs when used in RNA applications.

The following image shows an example diagram for RNA set up

      NOTE : By default, the Cascade command is enabled in the Rack PDU configuration file and default mode of the Rack PDU is RNA. Go to the Web UI (or your management software) to manage and control the Rack PDUs in the Cascade.

      Please refer to page 72 and 73 of the attached document to see how to configure Cascading or RNA.

      If you have any clarifications and/or requests for the above mentioned available information, please feel free to contact us at 1-800-800-4272 or chat with our technical support representatives.

      施耐德電機Taiwan

      附件
      NetShelter® Rack PDU Advanced.pdf [4.39 MB]
      探索更多
      產品:
      探索更多
      產品:

      需要協助?

      • 產品選型工具

        快速輕鬆地為您的應用找到合適的產品和附件。

      • 取得報價

        立即線上提交您的銷售需求,專業團隊將主動聯繫您。

      • 購買地點

        輕鬆在您所在地區找到最近的施耐德電機經銷商。

      • 支援中心

        在同一位置找到滿足您所有需求的支援資源。

      • 產品文檔
      • 軟體下載
      • 產品選型工具
      • 產品替代和替換
      • 幫助和聯絡中心
      • 尋找我們的辦公室
      • 取得報價
      • 人才招募
      • 公司簡介
      • 舉報不當行為
      • 無障礙
      • 新聞中心
      • 投資者
      • 專業洞察
      • 台灣施耐德電機學院
      • 綠色影響力落差調查
      • Schneider Go Green 2025
      • 隱私政策
      • Cookie通告
      • 使用條款
      • Change your cookie settings