Issue:
On an ATV630, the drive ramps all the way to low speed and high speed when my +/- speeds are pulsed.
Product Line:
Altivar Machines, Altivar Process Drives
Environment:
All models and serial numbers
Cause:
Drive ramps all the way up and down without stopping in between
Resolution:
This could be caused by any of the following:
On an ATV630, the drive ramps all the way to low speed and high speed when my +/- speeds are pulsed.
Product Line:
Altivar Machines, Altivar Process Drives
Environment:
All models and serial numbers
Cause:
Drive ramps all the way up and down without stopping in between
Resolution:
This could be caused by any of the following:
- The pulse isn't actually a pulse. Instead you're providing a sustained signal to the digital input
- Acceleration time is too short. +/- speed ramping is based on acceleration speed
- The pulse doesn't drop out long enough for the drive to recognize that it has dropped. Repeated input activation at too high speed can cause this
- Make sure you're actually pulsing the inputs for activation
- Try pulsing the inputs with a jumper wire from +24V to see if the behavior changes
- Adjust acceleration time longer
- Adjust deactivation of the digital inputs to a longer amount of time so the drive realizes the input has deactivated. The drive needs to see the signal drop in order to stop ramping
Опубліковано для: Schneider Electric Україна




Потрібна допомога?
Інструмент вибору продукту
Швидко та легко знаходьте потрібні продукти й допоміжне обладнання для своїх завдань.
Розрахувати вартість
Ставте свої запитання щодо продажів онлайн, і з вами зв’яжеться фахівець
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Довідковий центр
Знайдіть усі необхідні ресурси для підтримки в одному місці.